All,
I got the HV and DSC hooked up now so that the HV knows if the DSC is armed or disarmed(thanks
Kevin and Martin). And I got the Intercom installed and working. Not yet hooked up
to ECS but thats on the list.
I want to have ECS/HV be able to arm disarm the DSC if someone forgets to when going
to work / school and also at night / morning. I picked up some of the ELK sensitive
relays and figured out how to hook them up. The only question left is how big does the
external 12V power supply need to be? I have some old wall warts around that are rated
at 300ma 12V DC. Will they work or do I need something w/ a little more power.
Thanks,
Tom
----- Original Message -----
From: Kevin Keast
To: ecs-list@netbloc.com
Sent: Tuesday, December 14, 1999 6:18 PM
Subject: RE: [ECS] HV PC IO port hook-up
DON'T HOOK UP PORT A DIRECTLY TO A ZONE.
I have a HV-PC and use PORT A for controlling the relay for the keyswitch zone on
the DSC. PORT A can only DRIVE relays or CMOS circuits. IT IS NOT A RELAY ITSELF.
Port C could be used to drive a relay also if you specify it as an output.
I use a relay for the keyswitch zone because you need to "complete the circuit" for
the zone. I use ELK 924 SPDT Sensitive relays. They are really nice and have not
failed me. They require a separate 12V Power Supply. I also use these relays on my
garage door openers. Worthington Distributors has them for about $9 each. Craig also
has application notes on his website for quick easy setup.
Using CAT5 wire from your HV-PC to the relay should work fine.
Hope this helps,
Kevin
-----Original Message-----
From: Tom Hutchins [mailto:hutchins ta@fuse.net]
Sent: Tuesday, December 14, 1999 1:48 PM
To: ecs-list@netbloc.com
Subject: Re: [ECS] HV PC IO port hook-up
Kevin / Martin,
Sounds great! I just got all of my HV IO ports run to a wiring closet & terminated.
Now I'm trying to figure out how to make use of them. I think I understand the DSC alarm
status, simply connect one contact from the low output PGM1 to input #1 PORT B and the
other to the PORT B ground.
However, I am confused about the ability to arm / disarm the system, I thought I
could simply hook up a connection from either PORT A or PORT C to an unsed zone and
define it as a keyswitch zone. But you both speak of a relay being necessary to accomplish
this. I assume therefore that only PORT A is usable, but I'm still a little fuzzy about
the hook up. I thought that PORT A was a relay. But since you both discuss an external
relay ie. ELK / Prarie Digital I guess I'm wrong. Could one or both of you please enlighten,
me on this. Is there an external power source needed? If so what kind and can any relay
be used or would you recommend ELK / PD.
Sorry for all the questions, but since I'm obviously confused I don't want to hook
up anything wrong and fry the HV or the DSC.
Thanks,
Tom
----- Original Message -----
From: Kevin Keast
To: ecs-list@netbloc.com
Sent: Monday, December 13, 1999 10:24 PM
Subject: RE: [ECS] HV PC IO port hook-up
Hello All,
I have the DSC 832 (PC5010) and the intercom system(PC5928) and the low current
8 output module (PC5208).
I have a keyswitch zone which allows arming/disarming of the system: The HV output
is directly connected to an ELK relay that closes for 3 seconds (just like what Martin
Terry has ). The relay is connected to one of the DSC 832 zones to arm/disarm the system.
NOTE: I had to use a EOL resistor 5.6K ohms did the trick. See page 11 of PC5010 Installation
manual.
I have one of the DSC 832 low power outputs going directly to a HV-PC input -
this is programmed to tell me if the system is armed or not.
Intercom:
I have three intercoms on the system right now. I am using the radio/aux input
feature for ECS to speak to the house "works super!". I have the output of the sound
card signal connected to the " " terminal and the ground to ground - Only problem is
that I get a low hiss on the intercom stations - DOES ANYONE KNOW HOW TO FIX THIS?
SR: I have trained MS SDK using the intercoms. The first time: with great results,
the second: not so great. Since then SDK has not functioned properly (I have never
had much luck with this). I am determined to eventually get it working though. Another
problem is that you can only tap the microphone input for one of the intercom stations
( I Think ). So I am thinking that a microphone mixer will be needed at some point
to combine inputs.
That is about it right now. I love the DSC 832 so far. Good Luck and keep in
touch with your progress!
General Question: How do I wire up the zone -following function? Can I run the
zone right into my HV-PC?
Kevin
-----Original Message-----
From: Tom Hutchins [mailto:hutchins ta@fuse.net]
Sent: Sunday, December 12, 1999 12:19 PM
To: homevision-users@warren.mentorg.com; ecs-list@netbloc.com
Subject: [ECS] HV PC IO port hook-up
All,
I want to set up my HV-PC / ECS system to interface with my security system
(DSC Power 832). I want to run the HV ports to a wiring closet so that I can home run
wiring from there. My question is can I simply run 4 pair cat 5 cable from the HV itself
to a terminal strip in my wiring closet and from there to the security system ect (I
realize it won't be ' CAT 5' any more but I already got the wire)? Also, does each port
require a separate ground / common or can all be tied together.
Has any one out there tried this combination? I want to use ECS to determine
if the system is armed or not and arm it at the appropriate times. I also want to have
certain things happen depending on if the system is armed / disarmed in the away / stay
mode based upon the time of day, turn on/off lights ect. I also would like it to do
certain things depending on who arms / disarms (wife / kids each have their own code).
Last but not least I want ECS to phone me in the event of alarm with seperate messages
for intruder / fire / CO ect.
I know its alot but what the hey, Christmas vacation is coming up so I'll have
a little time to play.
PS. I have the DSC 832 intercom system installed and would like to pipe background
xmas music / CID / ECS messages through the system as well as use the built in mics
for speech recognition. Any thoughts?
Thanks,
Tom
----- Original Message -----From: Kevin KeastSent: Tuesday, December 14, 1999 6:18 PMSubject: RE: [ECS] HV PC IO port hook-upDON'T HOOK UP PORT A DIRECTLY TO A ZONE.I have a HV-PC and use PORT A for controlling the relay for the keyswitch zone on the DSC. PORT A can only DRIVE relays or CMOS circuits. IT IS NOT A RELAY ITSELF. Port C could be used to drive a relay also if you specify it as an output.I use a relay for the keyswitch zone because you need to "complete the circuit" for the zone. I use ELK 924 SPDT Sensitive relays. They are really nice and have not failed me. They require a separate 12V Power Supply. I also use these relays on my garage door openers. Worthington Distributors has them for about $9 each. Craig also has application notes on his website for quick easy setup.Using CAT5 wire from your HV-PC to the relay should work fine.Hope this helps,Kevin-----Original Message-----
From: Tom Hutchins [mailto:hutchins ta@fuse.net]
Sent: Tuesday, December 14, 1999 1:48 PM
To: ecs-list@netbloc.com
Subject: Re: [ECS] HV PC IO port hook-upKevin / Martin,Sounds great! I just got all of my HV IO ports run to a wiring closet & terminated. Now I'm trying to figure out how to make use of them. I think I understand the DSC alarm status, simply connect one contact from the low output PGM1 to input #1 PORT B and the other to the PORT B ground.However, I am confused about the ability to arm / disarm the system, I thought I could simply hook up a connection from either PORT A or PORT C to an unsed zone and define it as a keyswitch zone. But you both speak of a relay being necessary to accomplish this. I assume therefore that only PORT A is usable, but I'm still a little fuzzy about the hook up. I thought that PORT A was a relay. But since you both discuss an external relay ie. ELK / Prarie Digital I guess I'm wrong. Could one or both of you please enlighten, me on this. Is there an external power source needed? If so what kind and can any relay be used or would you recommend ELK / PD.Sorry for all the questions, but since I'm obviously confused I don't want to hook up anything wrong and fry the HV or the DSC.Thanks,Tom----- Original Message -----From: Kevin KeastSent: Monday, December 13, 1999 10:24 PMSubject: RE: [ECS] HV PC IO port hook-upHello All,I have the DSC 832 (PC5010) and the intercom system(PC5928) and the low current 8 output module (PC5208).I have a keyswitch zone which allows arming/disarming of the system: The HV output is directly connected to an ELK relay that closes for 3 seconds (just like what Martin Terry has ). The relay is connected to one of the DSC 832 zones to arm/disarm the system. NOTE: I had to use a EOL resistor 5.6K ohms did the trick. See page 11 of PC5010 Installation manual.I have one of the DSC 832 low power outputs going directly to a HV-PC input - this is programmed to tell me if the system is armed or not.Intercom:I have three intercoms on the system right now. I am using the radio/aux input feature for ECS to speak to the house "works super!". I have the output of the sound card signal connected to the " " terminal and the ground to ground - Only problem is that I get a low hiss on the intercom stations - DOES ANYONE KNOW HOW TO FIX THIS?SR: I have trained MS SDK using the intercoms. The first time: with great results, the second: not so great. Since then SDK has not functioned properly (I have never had much luck with this). I am determined to eventually get it working though. Another problem is that you can only tap the microphone input for one of the intercom stations ( I Think ). So I am thinking that a microphone mixer will be needed at some point to combine inputs.That is about it right now. I love the DSC 832 so far. Good Luck and keep in touch with your progress!General Question: How do I wire up the zone -following function? Can I run the zone right into my HV-PC?Kevin-----Original Message-----
From: Tom Hutchins [mailto:hutchins ta@fuse.net]
Sent: Sunday, December 12, 1999 12:19 PM
To: homevision-users@warren.mentorg.com; ecs-list@netbloc.com
Subject: [ECS] HV PC IO port hook-upAll,I want to set up my HV-PC / ECS system to interface with my security system (DSC Power 832). I want to run the HV ports to a wiring closet so that I can home run wiring from there. My question is can I simply run 4 pair cat 5 cable from the HV itself to a terminal strip in my wiring closet and from there to the security system ect (I realize it won't be ' CAT 5' any more but I already got the wire)? Also, does each port require a separate ground / common or can all be tied together.Has any one out there tried this combination? I want to use ECS to determine if the system is armed or not and arm it at the appropriate times. I also want to have certain things happen depending on if the system is armed / disarmed in the away / stay mode based upon the time of day, turn on/off lights ect. I also would like it to do certain things depending on who arms / disarms (wife / kids each have their own code). Last but not least I want ECS to phone me in the event of alarm with seperate messages for intruder / fire / CO ect.I know its alot but what the hey, Christmas vacation is coming up so I'll have a little time to play.PS. I have the DSC 832 intercom system installed and would like to pipe background xmas music / CID / ECS messages through the system as well as use the built in mics for speech recognition. Any thoughts?Thanks,Tom